Heat Shrink Cable Accessories >> Heat Shrink Termination Kits and Splices up to 35kV

Heat Shrink Termination Kits and Splices up to 35KV

 

Features:

Ÿ           Designed for 1,2,3,4 and 5-core XLPE, EPR, and MI/MIND paper insulated cables for the Electrical Utility, Commercial and Industrial Markets.

Ÿ           Insulating and sealing systems allow power cables to perform to a range of exacting requirements

Ÿ           Fast, Easy and Safe Installation

Ÿ           Meets or exceeds IEC60502.4, GB/T12706.4, JB/T8144

Ÿ           Suitable for a variety of low voltage electrical and mechanical applications

Ÿ           Indoor and outdoor are available

 

Material Features

Item

Unit

1KV

10KV or 35KV

Insulating Sheath

Insulating Material, Rain Shed, Bus Bar

Stress Control Cone

Electrical Material

Pull strength

Mpa

≥10

≥10

≥10

≥10

Elongation at Break

%

≥350

≥350

≥350

≥350

Brittle Temperature

<-30

<-40

/

<-40

Tracking Resistance

 

/

1A3.5

/

/

Specific Inductive Capacity

 

2.9

/

/

/

Volume Resistance

Ω·m

>1012

>1013

107~109

1~102

Compressive Strength

KV/mm

≥20

≥20

/

/

Oxygen Index

 

/

≥30

/

/

 

Technical Specification

Product Model

Items

Requirements

Results

Remarks

1kv Heat Shrink Cable Terminations and Splices

AC withstand

voltage test

No breakdown nor flashover shall occur at 4kv for 1 min

No breakdown nor flashover shall occur at 4kv for 1 min

PASS

Heating cycle voltage test

Heated for 5 hours,

Cooled for 3h, Heating at the temperature of 95

During 3 cycles at conductor temperature of 90 to 95

Approved by bellow

tests

AC withstand

voltage test

No breakdown nor flashover shall occur at 2.4kv for 4h

No breakdown nor flashover shall occur at 2.4kv for 4h

PASS

10kv Indoor /Outdoor Heat Shrink Cable Terminations and Splices

AC withstand

voltage test

No breakdown nor flashover shall occur at 45kv for 1 min

No breakdown nor flashover shall occur at 545kv for 1 min

PASS

Partial discharge test

13kv,≤20pc

15kv, ≤1pc

PASS

Heating cycle voltage test

Heated for 5 hours,

Cooled for 3h, Heating at the temperature of 95

During 3 cycles at conductor temperature of 90 to 95

Approved by bellow

tests

Partial discharge test

13kv,≤10pc

15kv, ≤1pc

PASS

Impulse withstand voltage test

1.2/50 u s±10 times

105kv, ±10 times

PASS

Cathode DC voltage test

No breakdown nor flashover shall occur at 52kv for 15 min

No breakdown nor flashover shall occur at 52kv for 15 min

PASS

AC withstand

voltage test

No breakdown nor flashover shall occur at 35kv for 4 h

No breakdown nor flashover shall occur at 35kv for 4 h

PASS

35kv Indoor /Outdoor Heat Shrink Cable Terminations and Splices

AC withstand

voltage test

No breakdown nor flashover shall occur at 105kv for 1 min

No breakdown nor flashover shall occur at 105kv for 1 min

PASS

Partial discharge test

39kv,≤20pc

39kv, ≤1pc

PASS

Heating cycle voltage test

Heated for 5 hours,

Cooled for 3h, Heating at the temperature of 95

During 3 cycles at conductor temperature of 90 to 95

Approved by bellow

tests

Partial discharge test

39kv,≤10pc

39kv, ≤1pc

PASS

Impulse withstand voltage test

1.2/50 u s±10 times

250kv, ±10 times

PASS

Cathode DC voltage test

No breakdown nor flashover shall occur at 156kv for 15 min

No breakdown nor flashover shall occur at156kv for 15 min

PASS

AC withstand

voltage test

No breakdown nor flashover shall occur at 104kv for 4 h

No breakdown nor flashover shall occur at 104kv for 4 h

PASS

 

1KV Heat Shrink Cable Accessories Guide

Applicable Section(mm2)

1-core(2-core3-core4-core5-core) Heat Shrink Termination

1-core(2-core3-core4-core5-core) Heat Shrink Splice

Bellow 16

RS-1/1(2345).0

JRS-1/1(2345).0

2550

RS-1/1(2345).1

JRS-1/1(2345).1

70120

RS-1/1(2345).2

JRS-1/1(2345).2

150240

RS-1/1(2345).3

JRS-1/1(2345).3

300630

RS-1/1(2345).4

JRS-1/1(2345).4

 

10KV and 35KV Heat Shrink Cable Accessories Guide

Voltage Grade

Applicable Section(mm2)

3-core(1-core) Heat Shrink Indoor(Outdoor) Termination (Splice)

8.7/15kV

2550

N(W.J)RS-20/3(1).1

70120

N(W.J)RS-20/3(1).2

150240

N(W.J)RS-20/3(1).3

300630

N(W.J)RS-20/3(1).4

26/35kV

50120

N(W.J)RS-35/3(1).1

150300

N(W.J)RS-35/3(1).2

400630

N(W.J)RS-35/3(1).3

 

 
 

| HOME | ABOUT US | PRODUCTS | WHAT'S NEW | CONTACT US | Email:international@zjwanma.com