Cold Shrink Cable Accessories >> 10kV Silicone Rubber Cold Shrink Indoor(Outdoor) Termination

 

 

                                

           Indoor                                                                  Outdoor

 

10KV Silicone Rubber Cold Shrink Termination

 

Features:

Ÿ           Adopt imported liquid silicone rubber from Germany, with reliable insulation and high-recovery elasticity

Ÿ           Unique Hi-K stress control material, self-recovery and pre-stretched technology Cold shrink delivery system allows quick easy installation without flame, special tools or extensive training.

Ÿ           The product is pre-stretched on a removable core. Removal of the core after positioning the termination allows the product to shrink into position, providing a tight seal.

Ÿ           Once installed, cold shrink termination creates a dynamic, compressive environmental seal and electrical interface without sealants or adhesives.

Ÿ           Wanma Cold Shrink Termination will retain its interface pressure for more than 30 years, based on accelerated life testing.

Ÿ           Meets or exceeds IEC60502.4, GB/T12706.4, JB/T8144

Ÿ           Can be used on a wide range of cable insulations in a variety of applications

Ÿ           Indoor and outdoor are available

 

Silicone Rubber Features

Index

Unit

Insulated Silicon Rubber

Conduction Silicon Rubber

Pull strength

Mpa

≥1.0

≥6.0

Part Tensile strength rate

%

≥800

≥550

Tearing strength

N/mm

≥30

≥18

Anti short circuit

 

1A4.5

/

Dielectric constant

 

<3.5

/

Electric volume resistivity

ΩCm

>1014

<100

Tensile set

 

≤5%

 

 

Technical Specification

Product Model

Items

Requirements

Results

Remarks

10kV Silicone Rubber Indoor and Outdoor Terminations

 

AC withstand

voltage test

No breakdown nor flashover shall occur at 45kv for 1 min

No breakdown nor flashover shall occur at 45kv for 1 min

PASS

Partial discharge test

13kv,≤20pc

15kv, ≤1pc

PASS

Heating cycle voltage test

Heated for 5 hours,

Cooled for 3h, Heating at the temperature of 95

During 3 cycles at conductor temperature of 90 to 95

Approved by bellow

tests

Partial discharge test

13kv,≤20pc

15kv, ≤1pc

PASS

Impulse withstand voltage test

1.2/50 u s±10 times

105kv, ±10 times

PASS

Cathode DC voltage test

No breakdown nor flashover shall occur at 52kv for 15 min

No breakdown nor flashover shall occur at 52kv for 15 min

PASS

AC withstand

voltage test

No breakdown nor flashover shall occur at 35kv for 4 h

No breakdown nor flashover shall occur at 35kv for 4 h

PASS

 

Termination Selection Guide

Voltage Grade

Applicable Section(mm2)

3-core(1-core) Cold Shrink Indoor(Outdoor) Termination

External Insulation Diameter of Applicable Cables

8.7/15kV

2550

N(W)LS-10/3(1).1

15.620.0

70120

N(W)LS-10/3(1).2

19.524.6

150240

N(W)LS-10/3(1).3

24.030.0

300400

N(W)LS-10/3(1).4

29.036.8

500800

N(W)LS-10/3(1).5

36.046.0

 
 